HJ社区海角

Electric drain control valve


Product model: T968Y

Nominal diameter: DN50 ~ 300mm

Nominal pressure: pn2.5 ~ 6.4Mpa

Operating temperature: - 60 ~ 450 ℃

Main materials: WCB, WC6, 20CrMo

Driving mode: Electric

Design standard: GB / T17213

Inspection standard: GB / T4213

Flange standards: JIS B220、JB/T79、ANSI B16.5-1981、GB/T9113、HG20594-97、HG20618-97, etc



PRODUCT OVERVIEW

In order to improve the economy of the power plant, the steam turbine is equipped with regenerative system, that is, high and low pressure heater. In order to ensure that the heater operates with water level and prevent the steam extraction from the upper stage of the steam turbine from channeling into the next stage when the heater operates without water level, so as to reduce the efficiency of the steam turbine and the safety of the equipment, the drain control valve is set in the drain system of the heater, According to the water level signal of the heater, it automatically switches the drain valve and adjusts the opening of the valve to keep the water level of the heater within a certain range. The working conditions of drain control valve are very poor, and it works under two-phase fluid in many cases (i.e. steam water mixing state). Moreover, it operates under the throttling state, and the cavitation is quite serious. When the cavitation reaches a certain degree, it can not play the role of drain regulating valve. In this case, the heater can not guarantee the operation with water level, which reduces the economy of steam turbine operation. It can be seen that it is particularly important to select a drain regulating valve with small cavitation, low noise, simple structure and reliable performance.


WORKING PRINCIPLE

The electric drain regulating valve is composed of an electric actuator and a drain regulating valve. The input of the electric control valve is the DC electrical signal sent by the regulator, which is amplified by the servo amplifier and then drives the actuator to generate axial thrust and drive the action of the control valve, so as to cause the change of medium flow and adjust various parameters in the system. At the same time, the actuator sends a valve position signal for comparison with the servo amplifier to keep the regulating valve at the position corresponding to an input signal to complete the servo regulation task.


MAIN TECHNICAL PARAMETERS

Nominal diameterDN(mm) 50 80 100 150 200 250 300
Flow characteristics Approximate linearity, approximate equal percentage
Nominal pressurePN(MPa) 2.5/6.4
Connection typewelding
Equipped with actuator ZKD Type
Stroke L (mm) 57.6 88.2
Maximum differential pressure △ P (MPA) 0.5/3
Rated flow coefficient Cv 44 99 175 395 640 1000 1440
Operating temperature T (℃) ≤450 ≤450
Use media water

Note: 1. This model also has flange type, right angle type and flange right angle type. 2. It can also be equipped with pneumatic actuator or HQ intelligent actuator.


MAIN TECHNICAL PERFORMANCE INDEXES

projectTechnical performance index
Basic error (%) No more than±2.5
Return difference (%) ≤1.5
Dead band (%) ≤3
Leakage 0.01%×Valve rated capacity


MATERIAL OF MAIN PARTS

NameMaterial Science
Valve body WCB、WC6、20CrMo
Spool316 Stainless steel
Shrouded 17-4PH
Valve stem 17-4PH
Valve seat316 Stainless steel


MAIN OVERALL CONNECTION DIMENSIONS

Nominal diameterDN(mm) 50 80 100 150 200 250 300
H 860 918 918 918 1460 1690 1690
H1 120 248 248 248 360 470 470
L 300 372 372 372 490 610 610
D190 150 180 200 244 355 420
D276 104 127 168 210 270 320
D350 80 100 140 180 230 270